The LZN1000 Series two-wire input temperature transmitter is a high performance device that receives Thermocouple / RTD / W / mV input and output mA with HART communication protocol.
Three internal keys to set parameter. Zero span calibration can be achieved either by HART or keypad.

Category:
  • Updating time of output current in 90 ms
  • Backlit LCD display rotatable to any angle
  • Two years stability of 0.1%
  • Accuracy +/-0.1% of Span
  • Parameter setting by keypad directly
  • 4-20 mA output plus direct digital  HART communication
  • Automatic zero calibration by press-button
  • Explosion proof and weather proof housing
Inputs : Universal Input
Thermalcouple : T/C (K, S, B, E, J, T, R, N)……
RTD : CU50 / PT100, 2 / 3 / 4 wires……
mV : -128~128 mV / -1000~1000 mV……
Resistance : 0-600 Ω / 0-5000 Ω
Accuracy : +/-0.1% of span
Stability : +/-0.1% of span for 2 years
Temperature Effect : +/-0.1% of span per 10 °C
CJC Compensation : +/-0.5 °C
Simulation Output : 4-20 mA
Material
Wetted Parts : S.S. 304 / S.S. 316 / Has. C / Tantalum etc.
Housing : Low copper aluminum alloy (Sprayed with
light blue polyurethane paint)
Module Housing : Flame-resistant PC
Name / Tag Plate : Stainless Steel 304 / Stainless Steel 316
Process Connection : Threads / Flanges
Over Temp. Limit : 120% of Full Scale
Mounting : Direct mounting or bracket on 2″ Pipe
Humidity Limit : 0-100% Relative Humidity
Ambient Temperature : -25~85 °C
Vibration Effect : +/-0.05% of URL per g to 200 Hz in any axis
EMI / RFI Effect : Follow SAMA PMC 33.1 from 20-1000
MHz and for field strengths up to 30 V/m
Display : Backlit LCD rotatable to any angle
Display Function : 5 Digits programmable & 0-100% Bargraph
Display Unit : °C / °F / °R / °K
Setting Method
B Type : USB + PC software (windows system
C Type : HART signal
D Type : HART signal & keypad
Current Output : 4-20 mA 2 wires with HART Signal
Load : Rohm = (VDC-9) * 50
Power Supply : 9-36 VDC
Digital Communication : HART Protocol
Cable Entry : M20 Conduit Threads / 1/2″ NPT (Female)
Damping : 0-32 Seconds
Response Time : 100 ms
Turn on Time : 2 Seconds with minimum damping
Zero Calibration : Automatic zero calibration by press-button
Isolation : Input / Output / GND isolated to 480 VDC
Power Supply Effect : +/-0.005 of Span per V
Weight : 60 g (Converter only) with display
: 30 g (Converter only) without display
Protection Class : IP67 (Standard)
: Intrinsically Safe, Eex ia IIC T5 (Standard)
: Explosion proof, Ex d IIB T5
Sensor Connection : M27 * 2 (Female)